Aneesh Chandran | 3 minute read | 18 November 2025

Cable fault detection and auto-reclose blocking with Mixed Circuit Protection (MCP)

Distribuție Energie Electrică Romania (DEER) chose to underground parts of overhead line circuits to integrate a new substation within the Romanian power network. To ensure a high level of availability and resilience, DEER sought a practical solution to enable auto-reclosure functionality on this mixed line comprising overhead and underground sections.

Synaptec’s Mixed Circuit Protection (MCP) solution was selected and deployed, providing protection relays with the ability to immediately distinguish between faults on cable sections or overhead lines. This permitted auto-reclose actions to be blocked only in the case of cable faults, and permitted in the case of transient overhead line faults, improving circuit availability, reducing downtime and damage to nearby grid assets from fault current inrush.

Safely enable
auto-reclosure

MCP provides relays with the instantaneous data required to safely operate auto-reclose functionality on hybrid or mixed lines

Flexibly defined protection zones

MCP defines multiple, flexible zones, each with highly sensitive and discriminative operation using a differential protection function

Ultrafast response

Identify faults and issue time-sensitive trip and control commands to prevent catastrophic damage to cables and other equipment

DEER is a Romanian electricity distribution company operating under the Electrica Group, who operate over 41% of Romania’s electricity networks, serving 3.8 million customers. It manages the electricity distribution network across 18 counties in Romania, serving approximately 3.8 million customers.

The company is committed to modernising its infrastructure, enhancing energy efficiency, and integrating renewable energy sources to meet the evolving demands of the energy sector.

Elecon is an electrical installation specialist based in Romania, who help their customers connect to networks safely and efficiently.

The challenge

DEER is committed to modernising their electricity distribution infrastructure to improve resilience, increase capacity and reliably deliver power to customers across 18 counties in Romania.

As part of this improvement initiative, the 110 kV Remetea substation was commissioned midway through the Toplita-Gheorgheni distribution line. As DEER had converted the overhead line section to line-in, line-out underground cable circuits, they required a protection scheme that can differentiate between overhead and underground faults, which is not cost-effective with conventional technologies.

 

 

Our solution

Synaptec’s MCP solution provided DEER with a passive, no maintenance protection system, that provides auto-reclose functionality on a faulted cable section. This enabled the operator to easily identify faults, whilst reducing the frequency and duration of line interruptions, as well as improving the safety and availability of their network.

The solution utilised Distributed Electrical Sensing (DES), a precision measurement technology that allowed power operators to protect their networks with unprecedented flexibility. Using the existing optical fibre within the power network, DES made high fidelity measurements of current at many locations over distances of up to 60 km from the substation.

The entire sensor array is passive, meaning no control power, data networks or ongoing maintenance or recalibration is required at each sensing location. Installation is simple, as the sensors connect to industry-standard CTs, reducing equipment footprint and cost, as well as minimising the scheduled outage time to install.

Synaptec deployed an outdoor IP rated single-phase Passive Secondary Converter for Current (PSC-1-C) and a split core Current Transformer (CT) at each phase of the power cables at the remote transition tower, just below the cable sealing ends bushings, which connects back to the substation via existing optical fibre.

Two three-phase Passive Secondary Converters for Current (PSC-3-C), and two DES Interrogators were also rack-mounted in the substation, which connected to existing line protection CTs. Combining the Interrogators with twelve passive sensors created two discrete protection zones between GIS and the start of the overhead line section.

Once installation was complete, the DES Interrogators issued time-critical trip and control commands, using both conventional dry contact and IEC 61850 GOOSE, after identifying faults within 5 milliseconds, for their respective circuits.

This provided DEER with an instant and precision-based protection response, issuing auto-reclose blocking commands when faults are detected within the cable section, and permitting auto-reclose when the fault occurs in the overhead line section.

DES Interrogator installed in relay panel.

The Remetea substation.

Installation overview

 

Book a demo

Our solutions provide real-time, actionable insights to improve reliability and reduce operational costs. Discover how Synaptec can enhance your power system monitoring by speaking to one of our team today.

Country(Required)
Read our data privacy policy here. By registering above, you are opting in to our newsletter and communications.
This field is for validation purposes and should be left unchanged.

Related posts

Passive Secondary Converter (PSC)

Passive Secondary Converter (PSC)

Synaptec’s Passive Secondary Converter (PSC) combines industry-standard instrument transformers with Distributed Electrical Sensing (DES) technology, enabling remote circuits to be instrumented passively without data networks, control power, or expensive civil works.

read more
Synthesis

Synthesis

Synthesis® is a comprehensive visualisation and analytics platform, designed to take full advantage of the unique capabilities of Synaptec’s Distributed Electrical Sensing (DES) technologies.It allows the synchronised waveform outputs from Synaptec’s sensor arrays to...

read more
A new approach to mixed circuit protection

A new approach to mixed circuit protection

Following a severe blizzard in 1888, Hugh Grant, the Mayor of New York, decided to start a global trend of undergrounding power cables to avoid storm damage. Today, global use of underground power cables in transmission and distribution ranges from 20% of the UK’s...

read more

Sectors we support

Power grids

Renewables

Industrial